Description
Product Highlights
● Available in 500 x 500 x 20mm / 26mm
● Available in 600 x 600 x 26mm / 28mm / 30mm
● High-Density calcium sulfate core with 1500kg / m3
● GI Steel Sheet available in 0.3 / 0.4 / 0.5mm
● Structural Reinforcement to achieve better loading capacity
● Available for Corner Lock Installation
● Available for Gravity Lay Installation
SYSTEM PERFORMANCE CRITERIA
System performance criteria are the most important to consider because they represent the performance in a typical installation. Panel only criteria such as concentrated load is often used to specify floor systems however, the test is not representative of an actual installation because it is performed with the panel testing blocks, not actual understructure.
System Performance Criteria | ||||||
System Type | Static Loads | Rolling Loads | ||||
Panel | Concentrated Load |
Safety Factor (min.2.0) |
Ultimated load | Uniform Load | 10 Passes | 10,000 Passes |
ECS800 | 368kg/800lbs | Pass | 736kg/1600lbs | 1650kg/m2 | 318kg 700lbs |
275kg 600lbs |
ECS1000 | 454kg/1000lbs | Pass | 909kg/2000lbs | 2300kg/m2 | 368kg 800lbs |
318kg 700lbs |
ECS1250 | 568kg/1250lbs | Pass | 1136kg/2500lbs | 3300kg/m2 | 454kg 1000lbs |
368kg 800lbs |
*A tests are performed using CISCA’s Recommend Test Procedures for Access Floors with the exception of Design Load
1. Design load is tested using CISCA Concentrated Load test method on actual understructure instead of steel blocks. Design load is determined by taking the lesser value of ultimate load divided by two or the point at which permanent damage begins to occur (yield point).
2. Safety factor is the multiple of Design load to the Ultimate Load. International standards and Dawn Modular Floor recommend’ a minium of 2.
2. Safety factor is the multiple of Design load to the Ultimate Load. International standards and Dawn Modular Floor recommend’ a minium of 2.
INSTALLATION
The finished access floor wil be rigid, free from vibration and rocking panels within a 3mm level over the entire space. Panels will be accurately cut to fit around all permanent features. All whole panels will be completely interchangeable allowing for any future changes. The access foor will maintain these origina conditions when sufficient panels have been removed for normal underfloor access.
ADVANTAGES
● Enhanced durability: Encapsulated calcium sulphate raised access flooring is highly durable and long-lasting, capable of withstanding heavy loads and foot traffic. This is particularly important in commercial office buildings where there may be a large number of people moving around on the flooring on a daily basis.
● Improved fire safety: Calcium sulphate is an inherently fire-resistant material, and encapsulated calcium sulphate raised access flooring can help to improve the fire safety of a building. This can be particularly important in commercial buildings where there may be a greater risk of fire due to the presence of large numbers of people, electrical equipment, and other potential sources of ignition.
● Better acoustic performance: Encapsulated calcium sulphate raised access flooring can help to improve the acoustic performance of a building, reducing noise transmission between floors and improving overall sound insulation. This can be particularly important in commercial buildings where there may be a need for privacy and confidentiality, or where a quiet working environment is required.
● Enhanced flexibility and adaptability: Raised access flooring systems are designed to be highly flexible and adaptable, making it easier to reconfigure the layout of a space or install new equipment and services. This can be particularly important in commercial office buildings where businesses may need to adapt quickly to changing market conditions or new technologies.
● Improved fire safety: Calcium sulphate is an inherently fire-resistant material, and encapsulated calcium sulphate raised access flooring can help to improve the fire safety of a building. This can be particularly important in commercial buildings where there may be a greater risk of fire due to the presence of large numbers of people, electrical equipment, and other potential sources of ignition.
● Better acoustic performance: Encapsulated calcium sulphate raised access flooring can help to improve the acoustic performance of a building, reducing noise transmission between floors and improving overall sound insulation. This can be particularly important in commercial buildings where there may be a need for privacy and confidentiality, or where a quiet working environment is required.
● Enhanced flexibility and adaptability: Raised access flooring systems are designed to be highly flexible and adaptable, making it easier to reconfigure the layout of a space or install new equipment and services. This can be particularly important in commercial office buildings where businesses may need to adapt quickly to changing market conditions or new technologies.
Reviews